Seitenansicht 14
D-011-0093 13
12
Alarm Output Relay Mode icon.
During programming, indicates selection of energized or de-energized alarm
output relay state for the Zone being programmed.
Down arrow points to ENERGIZE when energized relay mode is selected
(relay is energized with no alarms; relay de-energizes upon alarm).
Down arrow points to DE-ENERGIZE when de-energized relay mode is
selected (relay is de-energized with no alarms; relay energizes upon alarm).
13
Water Presence Mode icon.
Indicates Zone is programmed for detecting presence of water.
Display Icons — continued
Index
No. Icon Function
Winland_English.fm Page 13 Wednesday, July 5, 2006 1:33 PM